HCA-YS3系列直流漏電流傳感器是應(yīng)用磁調(diào)制原理研制而成的一種新型電流傳感器,其輸出的穩(wěn)定性好,初、次級之間高度絕緣,用于訊號系統(tǒng)、線路檢測、電監(jiān)測系統(tǒng)等直流漏電流測量。( HCA-YS3 series of DC Leakage current sensor application of magnetic modulation principle from the development of a new type of current sensor, output stability between primary and secondary highly insulated for signaling systems, line detection, electrical monitoring DC Leakage current measurement.)
電氣參數(shù)(Electrical characteristics) |
|
型號Type |
HCA10
-YS3 |
HCA20
-YS3 |
HCA50
-YS3 |
HCA100
-YS3 |
HCA200
-YS3 |
HCA500
-YS3 |
|
Ipn |
額定輸入電流(DC)
Rated input |
±10 |
±20 |
±50 |
±100 |
±200 |
±500 |
mA |
Ipm |
測量電流范圍(DC) Measuring range |
±20 |
±40 |
±100 |
±200 |
±400 |
±1000 |
mA |
RL |
負(fù)載電阻
Load resistance |
≥10 |
KΩ |
Vout |
輸出電壓 Rated output voltage |
±5 |
V |
Vo |
零電壓失調(diào) Zero offset voltage |
<±50 |
mV |
Vc |
電源電壓
Supply voltage |
±15±5% |
V |
Ic |
靜態(tài)功耗 Current consumption |
≤60 |
mA |
Iot |
零點(diǎn)溫漂 Thermal drift of Io |
≤±1. 5 |
mV/℃ |
F |
帶寬Frequency bandwidth(-3dB) |
DC |
Hz |
εG |
精度 Accuracy |
1 |
% |
εL |
線性度 Linearity |
1 |
% |
Tr |
響應(yīng)時間 Response time |
≤200 |
mS |
Vd |
絕緣電壓 Insulation voltage |
2.5 |
KV |
Ta |
工作溫度 Ambient operating temperature |
-25~+70 |
℃ |
Ts |
儲存溫度 Ambient storage temperature |
-40~+85 |
℃ |
M |
重量 mass |
|
g |
|
標(biāo)準(zhǔn)tandards |
EN50178\IEC61010-1\UL94-Vo\ROHS |
|
使用說明Remarks
1、應(yīng)用:通訊電源、不間斷電源UPS、斬波器、電化學(xué)、整流、電源監(jiān)測、電焊機(jī)、變頻、開關(guān)電源、電池監(jiān)測、電動機(jī)監(jiān)測等領(lǐng)域。Application: communication power supply, uninterruptible power supply UPS chopper, electrochemical, rectifier, power monitoring, welding machines, inverter, switching power supply, battery monitoring, motor monitoring fields.
2、傳感器的輸出幅度可根據(jù)用戶需要進(jìn)行適當(dāng)調(diào)節(jié)。The amplitude of the output of the sensor can be appropriately adjusted according to user needs.
3、可按用戶需求定制不同額定輸入電流和輸出電壓的傳感器。Custom different rated input current and the output voltage of the sensor.
4、當(dāng)待測電流從傳感器穿過,即可在輸出端測得電流大小。(注意:錯誤的接線可能導(dǎo)致傳感器損壞)When the current to be measured is across from the sensor can be measured at the output current size. (Note: incorrect wiring may cause sensor damage)
下載詳細(xì)資料 HCA-YS3.pdf |