HKA-K1YDV系列霍爾電流傳感器的初、次級(jí)之間是絕緣的,可用于測(cè)量交流電流。
(HKA-K1YDV Series Hall-effect Current transducer between primary and secondary is insulated, can be used for the measurement of AC current)
電氣參數(shù)(Electrical characteristics) |
|
型號(hào)Type |
HKA30
- K1YDV |
HKA50
- K1YDV |
HKA100
- K1YDV |
HKA200
- K1YDV |
HKA400
- K1YDV |
HKA500
- K1YDV |
|
Ipn |
額定輸入電流(AC)
Rated input |
30 |
50 |
100 |
200 |
400 |
500 |
A |
Ipm |
測(cè)量電流范圍(AC) Measuring range |
60 |
100 |
200 |
400 |
800 |
1000 |
A |
Rm
|
負(fù)載電阻
Load resistance |
≥10 |
KΩ |
Iout |
輸出電壓 Rated output voltage |
5 |
V |
Io |
零電壓失調(diào) Zero offset voltage |
<±25 |
mV |
Vc |
電源Supply voltage |
24±5% |
V |
Ic |
靜態(tài)功耗 Current consumption |
≤40 |
mA |
Iot |
零點(diǎn)溫漂 Thermal drift of Io |
≤±1 |
mV/℃ |
F |
帶寬Frequency bandwidth(-3dB) |
20~20000 |
Hz |
εG |
精度 Accuracy |
1 |
% |
εL |
線性度 Linearity |
1 |
% |
Tr |
響應(yīng)時(shí)間 Response time |
≤200 |
mS |
Vd |
絕緣電壓 Insulation voltage |
2.5 |
KV |
Ta |
工作溫度 Ambient operating temperature |
-40~+85 |
℃ |
Ts |
儲(chǔ)存溫度 Ambient storage temperature |
-40~+125 |
℃ |
M |
重量 mass |
75 |
g |
|
標(biāo)準(zhǔn)Standards |
EN50178\IEC61010-1\UL94-Vo\ROHS |
|
使用說明Remarks
1、 應(yīng)用:通訊電源、不間斷電源UPS、斬波器、電化學(xué)、整流、電源監(jiān)測(cè)、電焊機(jī)、變頻、開關(guān)電源、電池監(jiān)測(cè)、電動(dòng)機(jī)監(jiān)測(cè)等領(lǐng)域。Application: communication power supply, uninterruptible power supply UPS chopper, electrochemical, rectifier, power monitoring, welding machines, inverter, switching power supply, battery monitoring, motor monitoring fields.
2、傳感器的輸出幅度可根據(jù)用戶需要進(jìn)行適當(dāng)調(diào)節(jié)。The amplitude of the output of the sensor can be appropriately adjusted according to user needs.
3、可按用戶需求定制不同額定輸入電流和輸出電壓的傳感器。Custom different rated input current and the output voltage of the sensor.
4、當(dāng)待測(cè)電流從變送器穿過,即可在輸出端測(cè)得電壓大小。(注意:錯(cuò)誤的接線可能導(dǎo)致變送器損壞)When the current to be measured is across from the transmitter can be measured at the output voltage size. (Note: incorrect wiring may cause transmitter damage)
下載詳細(xì)資料 HKA-K1YDV.pdf |