HKA-K3Y系列霍爾電流傳感器的初、次級之間是絕緣的,可用于測量直流、交流和脈沖電流。
(HKA-K3Y Series Hall-effect Current Sensor between primary and secondary is insulated, can be used for the measurement of DC, AC and pulse current)
電氣參數(shù)(Electrical characteristics) |
|
型號Type |
HKA1000
-K3Y |
HKA2000
- K3Y |
HKA3000
- K3Y |
HKA5000- K3Y |
A |
Ipn |
額定輸入電流
Rated input |
1000 |
2000 |
3000 |
5000 |
A |
Ipm |
測量電流范圍
Measuring range |
2000 |
4000 |
5000 |
8000 |
A |
Vout |
輸出電壓
Rated output voltage |
4 |
V |
Vo |
零電壓失調(diào)
Zero offset voltage |
<±25 |
mV |
VOM |
磁失調(diào)電壓
Magnetic offset voltage |
≤±25 |
mV |
RL |
負(fù)載電阻
Load resistance |
≥10 |
KΩ |
Vc |
電源電壓
Supply voltage |
±15±5% |
V |
Ic |
靜態(tài)功耗
Current consumption |
≤50 |
mA |
Vot |
零點(diǎn)溫漂
Thermal drift of Vo |
≤±0.5 |
mV/℃ |
F |
帶寬 Frequency bandwidth(-3dB) |
DC~20 |
KHz |
εG |
精度 Accuracy |
±1 |
% |
εL |
線性度 Linearity |
±1 |
% |
Tr |
響應(yīng)時間
Response time |
≤7 |
μS |
Vd |
絕緣電壓
Insulation voltage |
5 |
KV |
Ta |
工作溫度 Ambient operating temperature |
-40~+85 |
℃ |
Ts |
儲存溫度 Ambient storage temperature |
-40~+125 |
℃ |
M |
重量 mass |
520 |
g |
|
標(biāo)準(zhǔn)Standards |
EN50178\IEC61010-1\UL94-Vo\ROHS |
|
使用說明Remarks
1、 應(yīng)用:通訊電源、不間斷電源UPS、斬波器、電化學(xué)、整流、電源監(jiān)測、電焊機(jī)、變頻、開關(guān)電源、電池監(jiān)測、電動機(jī)監(jiān)測等領(lǐng)域。Application: communication power supply, uninterruptible power supply UPS chopper, electrochemical, rectifier, power monitoring, welding machines, inverter, switching power supply, battery monitoring, motor monitoring fields.
2、傳感器的輸出幅度可根據(jù)用戶需要進(jìn)行適當(dāng)調(diào)節(jié)。The amplitude of the output of the sensor can be appropriately adjusted according to user needs.
3、可按用戶需求定制不同額定輸入電流和輸出電壓的傳感器。Custom different rated input current and the output voltage of the sensor.